Cisco ONS 15310-CL and Cisco ONS 15310-MA Troubleshooting Guide, Release 9.0
78-18394-01
Chapter 2 Alarm Troubleshooting
Alarm Procedures
Clear the HLDOVRSYNC Alarm
Step 1 Clear additional alarms that relate to timing, such as:
• 2.7.98 FRNGSYNC, page 2-72
• 2.7.99 FSTSYNC, page 2-72
• 2.7.112 HLDOVRSYNC, page 2-79
• 2.7.135 LOF (BITS), page 2-92
• 2.7.149 LOS (BITS), page 2-101
• 2.7.170 MANSWTOINT, page 2-114
• 2.7.171 MANSWTOPRI, page 2-114
• 2.7.172 MANSWTOSEC, page 2-115
• 2.7.173 MANSWTOTHIRD, page 2-115
• 2.7.238 SWTOPRI, page 2-143
• 2.7.239 SWTOSEC, page 2-143
• 2.7.240 SWTOTHIRD, page 2-143
• 2.7.241 SYNC-FREQ, page 2-144
• 2.7.242 SYNCPRI, page 2-144
• 2.7.243 SYNCSEC, page 2-145
• 2.7.244 SYNCTHIRD, page 2-145
Step 2 Reestablish a primary and secondary timing source according to local site practice. If none exists, refer
to the “Change Node Settings” chapter in the Cisco ONS 15310-CL and Cisco ONS 15310-MA
Procedure Guide for procedures.
Step 3 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447) in order to report a Service-Affecting (SA)
problem.
2.7.113 I-HITEMP
Default Severity: Critical (CR), Service-Affecting (SA)
SONET Logical Object: NE
The Industrial High Temperature alarm occurs when the temperature of the ONS 15310-CL or
ONS 15310-MA is above 149 degrees F (65 degrees C) or below –40 degrees F (–40 degrees C). This
alarm is similar to the HITEMP alarm but is used for the industrial environment. If this alarm is used,
you can customize your alarm profile to ignore the lower-temperature HITEMP alarm.
Clear the I-HITEMP Alarm
Step 1 Complete the “Clear the HITEMP Alarm” procedure on page 2-78.