2-35
Cisco ONS 15310-CL and Cisco ONS 15310-MA Troubleshooting Guide, Release 9.0
78-18394-01
Chapter 2 Alarm Troubleshooting
Alarm Procedures
Clear the AUTOSW-UNEQ (VT-MON) Alarm
Step 1 Complete the “Clear the UNEQ-V Alarm” procedure on page 2-153.
Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447) in order to report a Service-Affecting (SA)
problem.
2.7.32 BAT-FAIL
Default Severity: Major (MJ), Service-Affecting (SA)
SONET Logical Object: PWR
The Battery Fail alarm occurs when the power supply is not detected. This could be because the supply
is removed or is not operational. The alarm does not distinguish between the individual power supplies,
so onsite information about the conditions is necessary for troubleshooting.
Clear the BAT-FAIL Alarm
Step 1 At the site, determine which battery is not present or operational.
Step 2 Remove the power cable from the faulty supply. The “Install the Cisco ONS 15310-CL” chapter and the
“Install the Cisco ONS 15310-MA” chapter in the Cisco ONS 15310-CL and Cisco ONS 15310-MA
Procedure Guide contains instructions for installing both AC (ONS 15310-CL only) and DC (ONS
15310-CL and ONS 15310-MA) power supply cables. To remove the cable, reverse the appropriate
procedure.
Caution Always use the supplied electrostatic discharge wristband when working with a powered ONS 15310-CL
or ONS 15310-MA.
Step 3 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447) in order to report a Service-Affecting (SA)
problem.